Earth Bonding Cable Size Selection
Guidance on earth conductor and protective bonding conductor cross-sectional areas is given in the guide to the wiring regulations BS7671.
BS 7671 lists five types of earthing system: TN-S, TN-C, TT, TN-C and IT.
T= Earth
N = Neutral
S = Separate
C = Combined
I = Isolated
The Earthing conductor and main protective bonding conductor sizes (copper equivalent) for TN-S and TN-C-S supplies are determined as follows:
Line Conductor or Neutral Conductor of PME supplied | mm2 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 |
Earthing Conductor not buried or buried and protected against corrosion and mechanical damage | mm2 | 6 | 6 | 10 | 16 | 16 | 16 | 25 | 35 |
Main Protective Bonding Conductor | mm2 | 6 | 6 | 6 | 10 | 10 | 10 | 16 | 25 |
Main Protective Bonding Conductor for PME supplies (TN-C-S) | mm2 | 10 | 10 | 10 | 10 | 10 | 10 | 16 | 25 |
Notes:
1. Protective conductors (including earth and bonding conductors) of 10mm² cross-sectional area or less shall be of copper.
2. The distributor may require a minimum size of earth conductor at the origin of the supply of 16mm² copper or greater for TN-S and TN-C-S supplies.
3. Buried earth conductors must be at least:
• 25mm² copper if not protected against corrosion
• 50mm² steel if not protected against corrosion
• 16mm² copper is not protected against mechanical damage but protected from corrosion.
• 16mm² coated steel is not protected against mechanical damage but protected against corrosion.
4. The distributor should be consulted when in doubt.
Buried | ||
---|---|---|
Unprotected | Protected against corrosion | Protected against corrosion and mechanical damage |
mm2 | mm2 | mm2 |
25 | 16 | 2.5 |
Not Buried | ||
Unprotected | Protected against corrosion | Protected against corrosion and mechanical damage |
mm2 | mm2 | mm2 |
4 | 4 | 2.5 |
Notes:
1. Assuming protection against corrosion by a sheath
2. The main protective bonding conductors shall have a cross-sectional area of not less than half that required for the earthing conductor and not less than 6mm².
Please be aware of the following:
a) Only copper conductors should be used: copper covered aluminium conductors or aluminium conductors or structural steel can only be used is special precautions outside the scope of the Wiring Guide are taken.
b) Bonding connections to incoming metal services should be made as near as practicable to the point of entry of the services into the premises, but on the consumer’s side of any insulating section.
c) Where practicable, the connection to the gas, water, oil, etc service should be within 600mm of the service meter, or a point of entry to the building if the service meter is external and must be on the consumer’s side before and branch pipework and after any insulating section in the service. The connection must be made to hard pipework, not to soft or flexible meter connections.
d) The connection must be made using clamps ( to BS 951) and be suitably protested against corrosion at the point of contact.
(taken from source: Onsite Guide : BS 7671:2008 +A3: 2015. 6th Edition)
People also ask
Earthing is a safety measure to prevent electric shock, whereas bonding is a term used for connecting together all the metallic parts that are not supposed to be carrying electric current ...
Cable size selection is based on 3 main factors: Current carrying capacity, Voltage regulation, Short circuit rating. Read more about the cable sizes and what determinate them...
The fault current is the electrical current which flows through a circuit during an electrical fault condition. A fault condition occurs when one or more electrical conductors short to each other or to ground...
Cable Portfolio
View our comprehensive range of power, data, control and instrumentation cables and accessories
Go